| Model | Explanation | |||
| KN01M | x | x | x | Switch value input, output |
| Channel | S | Signal | ||
| D | Dual | |||
| Input | C | Passive switch input | ||
| S | Proximity switch input(8.2V supply) | |||
| Output | J | Relay output | ||
| N | Transistor collector output | |||
| Transmit accuracy | ±0.2%×F.S |
| Danger area | Passive input signal is pure switch contact. |
| Allowable input signal | Active signal: Sn = 0 , Current< 0 . 2mA; Sn is infinite,current< 3mA ; Sn is max.sensing distance,current is 1.0-1.2mA |
| Safety area output signal |
Relay NC( NO) contact point output, allow( Resistive) load: AC125V 0.5A,DC60V 0.3A,DC30V 1A Open collector output: Passive,outer supply:< 40V DC , switch frequency≤ 5kHz . Current output≤ 60mA , short circuit current< 100mA . |
| Applicable | Proximity switch,active and passive switches, dry contact (intrinsically safe pressure switch |
| Power supply | DC 24V±10% |
| Power consumption | 2W |
| Housing size | W× H× D( 22 . 6 * 100 . 3 * 113 . 3 ) mm |